The WLDS600 positioning transmission leak sensor is a high-performance liquid leak detection device. It can detect leaks of water, weak acids, weak bases and other liquids. The module monitoring cable is up to 200 meters long. Once a liquid leak is detected, the leakage location will be displayed on the screen and relay contact signals will be output. The WLDS600 module can be used as a standalone leak detection alarm unit or can be networked with other WLDS6000 modules. The module can communicate with other main monitoring systems or other upper computers through various standard communication protocols to achieve remote alarm and control of remote devices. Widely used in communication base stations, computer rooms, hotels, warehouses, restaurants, libraries, archives, equipment cabinets, and other places that require water leakage alarms.
Product Details
Technical specifications
| working power supply | 12~24VAC | quiescent current | <45mA | alarm current | <60mA |
| accuracy | Detect 0.5% ± 0.5 meters of cable length | response time | Less than 1 second | ||
| Detecting cables | ASC6100 Four core Positioning Detection Cable | ||||
| Detecting cable length | The maximum cable length that can be wired is 200 meters | ||||
| communication protocol | RS485 serial interface (dual line network), MODBUS communication protocol | ||||
| relay output | 1A, 24VDC or 125VAC, 0.5A rated value (normally open and normally closed) | ||||
| working environment | -20~70 ℃, 10~90% RH (non condensing) | ||||
| storage environment | -20~80 ℃, 10~90% RH (non condensing) | ||||
| cable connection | Connect the cable to the detection module and the detection cable. | ||||
| Installation Method | Meets the 86 box installation size and supports wall and floor mounting. | ||||
| Environmental standards | RoHS、Reach | ||||
| plastic casing | White PVC, NEMA1, IP55 | ||||
Indicator light description:
The A power indicator light (green LED) displays the power on status of the system.
The B fault indicator light (yellow LED) shows that the system has detected a cable connection error or a fault in my circuit.
The C leakage indicator (red LED) displays that the system has detected a leakage situation.
D display LCD screen: The digital display shows the distance of the leakage location.
When the reset button (red button) triggers an alarm, pressing this button can manually eliminate the alarm state
Online Inquiry
Industry Applications
Recommended Products

Phone: 0755-83343508/0755-28030573
Fax: 0755-83356166
Email: ming@greystoneenergy.com.cn
Address: 2nd Floor, Building 10, Shenliang Guanlan Automotive Electronics Characteristic Industrial Park, 299 Guanping Road, Longhua District, Shenzhen